Robust Fuzzy-PID Technique for the Automatic Generation Control of Interconnected Power System with Integrated Renewable Energy Sources
##plugins.themes.bootstrap3.article.main##
This paper proposes a robust hybrid fuzzy PID controller, with the PID gain values tuned using the particle swarm optimization (PSO) technique for the automatic generation control (AGC) of the two-area hybrid power system. PSO Algorithm is applied to reduce the integral of time-weighted absolute error (ITAE) of the frequency and tie-line power variations of the two-area interconnected power system. The suggested method’s efficacy is examined on an interconnected two-area power system with Area 1 containing thermal reheat plants, hydropower plants, and diesel generating units, and Area 2 comprising thermal reheat plants and renewable energy sources (RES): wind energy conversion system, solar photovoltaic system, and electric vehicles. The thermal reheat power plants are modelled taking into consideration the governor dead band (GDB) and the generation rate constraints (GRC). The performance of the presented controller is compared with the genetic algorithm-optimized PID AGC and the PSO-optimised PID AGC. The simulation outcomes show superior results of the proposed controller against other controllers. Further, sensitivity analysis reflects that the proposed technique provides better dynamic response and robustness than the other techniques.
Downloads
Introduction
In the electrical power grid, maintaining a consistent power supply and demand is vital to enhance the quality, reliability and stability of the power grid. Failure to control the power generated against power demand following a sudden load change or power system disturbance will lead to frequency deviation of the power system from its nominal values and in some cases to a total blackout of the power system [1]. Moreover, power grids are becoming more complex and the integration of RES, such as wind plants, solar and tidal turbines into multi-area hybrid power systems has increased significantly in recent years. In addition, the emersion of new concepts like micro-grids and smart grids has increased both the complexity and uncertainty of modern power grids [2]. The main goal of AGC is to automatically control any variation of frequency tie-line power to zero and keep their values consistent with their nominal predefined values [3]. Recently, several advanced methods have been introduced for AGC in multi-area conventional as well as hybrid power grids. Classical controllers such as PID controllers have been used to manage frequency and tie-line power changes [4]. Although classical controllers have a simple design and are well-investigated controllers for AGC, drawbacks such as their weak dynamic response, inaccurate results, long settling time and dependency on trial-and-error procedures limit their applications [2]. Fractional order PID controllers have also been proposed over conventional integral controllers for AGC [5]. The major drawbacks of fractional order controllers are their increased computational requirements and complexity [6]. The other advanced control techniques proposed in the literature include sliding mode controllers [7], H-infinity controllers [8] and model predictive control approaches [9]. The drawbacks of these controllers are their complexity, and uncertainty in their performance, and further, these are not commonly utilized in the industry [10]. Heuristic methodologies like genetic algorithm [11], particle swarm optimization techniques [12], differential evolution algorithm [13], firefly algorithm [14], and grey wolf optimization algorithm [15], have been used to optimize PID gain parameters. However, mostly these optimization approaches are applied in conventional power systems without considering the renewable energy sources and any of the nonlinear constraints of the system components [10]. Many researchers have introduced cascaded controllers, which consist of two controllers, one of which is positioned inside the feedback loop of the other, and the output of the first controller acts as the set-point for the second.
The major drawbacks of the cascaded controllers are the time consumption, the high level of tolerance required, and the complexity of its design [6]. The developments in artificial intelligence have increased significantly and artificial neural network (ANN) controllers have been utilized which update the training sets based on continuous learning. Moreover, the knowledge of the controller is updated continuously via a set of training rules resulting in estimation convergence to zero. ANN-based controllers have been used for AGC in interconnected hybrid power systems using several algorithms such as fractional order ANN Controller [16] and ANN-tuned PID controller [17]. Tilt integral derivative controllers (TID) give better performance compared to conventional controllers [2]. TID has been used for AGC of power systems using several algorithms like fractional order TID controller using pathfinder algorithm [18] and hybrid modified particle swarm optimization with genetic algorithm [19]. The major drawbacks of TID controllers are that these controllers take more time to achieve a stable state and more numbers of control parameters are needed to be tuned in the optimization process [20]. Research interest in the fuzzy logic approach to system dynamics control has increased because of its reasonably wide application range and its fast response. Fuzzy logic Controllers and ANFIS controllers have been introduced in [21], [22]. However, a fuzzy system alone requires a lot of experience for tuning the membership functions. Therefore, the best dynamic performance of fuzzy logic control has been achieved by utilizing optimization techniques [23]. Thus, several publications are there in the field of AGC of power systems. In this paper, a hybrid PSO-fuzzy PID controller is suggested to optimize PID gain values for the AGC of a two-area interconnected power grid comprising thermal reheat, hydro, diesel, wind and solar photovoltaic power plants together with electric vehicles. PSO method is utilized to obtain the best PID gain parameters enabling the fuzzy logic controller to provide optimal response.
The paper is arranged as follows: Description and component modeling of the hybrid power system is introduced in the following section followed by an overview of the GA-PID AGC and PSO-PID AGC in Section 3. Section 4 discusses the proposed PSO-optimized fuzzy-PID AGC design followed by the test system data and the simulation outcomes with discussion in Section 5 and the conclusion in Section 6.
System Description and Modelling
The system investigated is composed of two different areas connected with each other. Area 1 comprises thermal plants with reheat turbines, hydro plants and diesel generators while Area 2 integrates wind power plants, solar photovoltaic systems, and electric vehicles altogether with thermal power plants. Fig. 1 represents the AGC block diagram for the suggested power system model under study.
Area control error (ACE) corresponding to Areas 1 and 2 are: where
and : bias parameters of areas 1 and 2, respectively.
and : frequency variation in areas 1 and 2, respectively. where
Ri: regulation parameter of the turbine-generator unit.
Di: frequency dependency of load.
The modelling aspects of various system components are given in this section.
Thermal Power Plant
The representation of a thermal reheat model taking into consideration (GRC) and (GDB) is illustrated in Fig. 2 [24], [25].
Hydro Power Plant
The representation of a hydro plant model is illustrated in Fig. 3 [26].
Diesel Generating Unit
The representation of a diesel generator is illustrated in Fig. 4 [27].
Solar Photo-Voltaic Energy Conversion System
The transfer function of a solar PV plant with a maximum power point tracking facility (MPPT) is shown in Fig. 5 [10].
Wind Energy Conversion System
The output power generated from wind system is represented by: where
: air density.
Asr: blade swept area.
Cp: power coefficient.
: wind velocity.
The transfer function of the wind system is: where
and : gains of the wind system.
and : time constants of the wind system [10].
The system block diagram is shown in Fig. 6.
Battery Energy Storage System (BESS)
The intermittent nature of the power outputs from wind and solar PV systems can be managed to a certain extent by the provision of a BESS. The transfer function of BESS is illustrated in Fig. 7: [28].
Electric Vehicle Charging System
Converters in electric vehicles (EVs) have become a reliable backup for frequency support in power systems due to their bidirectional connection capabilities [29]. In this paper, the linearized model, as shown in Fig. 8 [30] is used to represent EV System.
GA and PSO Techniques—An Overview
To attain the optimum AGC performance, it is important to choose an objective function to be minimized to optimize the gain values of the PID controller accordingly. The major performance indices commonly utilized for optimizing PID parameters of the AGC are absolute error integral (IAE), integral of time multiplied by absolute error (ITAE), integral of squared error (ISE), and integral of time multiplied by squared error (ITSE) [31] These are given by:
where and are weighting for frequency and tie-line power errors respectively in both areas which are used to provide importance index. these variables are given an appropriate weightage in the equations. In the current work, ITAE is considered as the fitness function to improve the PID gain parameters of the AGC. Thus, the ITAE is: [32]
Particle Swarm Optimization (PSO)
PSO is a stochastic optimization algorithm based on swarm of birds and schooling of fish. It is processed by the imitation of a bird flocking in multiple-dimensional area. Every particle is represented by a position (x) and velocity vectors (v). The particle is updated based on its position and its velocity information. In every iteration, the particle is evaluated via ITAE fitness function to obtain its best value (Pbest) and its position. Further, every particle has the optimum value so far in the group (Gbest) out of Pbest of all particles. Position and velocity of the particle are updated as [32]
where k is the iteration number, i is the particle index, Pbest is the global best solution, x1 and x2 are acceleration factors, ra1 and ra2 are uniformly random numbers, and w is inertia weight. The particle swarm optimization algorithm proceeds as follows:
- Initialize the positions and velocities of particles, also population size, iteration number, and upper and lower bounds of controller variables.
- Calculate the ITAE fitness function of each particle.
- Assign The minimum function value as Pbest, and the best fitness function value among the all Pbest as Gbest.
- Utilize (17) and (18) in each iteration and update x and v of the particles, respectively.
- If the stopping criteria are reached, proceed to the last step 6. Otherwise, return to step ii and repeat the procedure.
- In the last iteration, the optimum controller parameters are obtained by the minimum objective function which is the latest Gbest [33].
Genetic Algorithm (GA)
GA is an optimization technique used to optimize the PID controller gains due to its high optimization capability that guarantees the survival of the fittest. GA had been developed by the natural selection principle, a biological method where the stronger individual has a high probability of winning against weaker individuals. The technique begins with an initial random population of chromosomes, each chromosome consisting of genes represented by binary bits. These bits are appropriately decoded and mapped to give an appropriate string for the optimization problem. The initial population is then regenerated to obtain the new population and to converge to the fittest individuals by the utilization of the fitness function. The fitness function gives a value to each chromosome. After that, the outcomes are organized, and elected strings are selected to produce a new generation. GA applies selection, crossover and mutation to converge at the global optimum and to improve the selected individuals [11], [28]. To make a high correlation between parents and offspring, there is a need for a repair function which is necessary for defining the initial population of genetic algorithm individuals, mutation and crossover operators. AGC focuses on power flow balancing and frequency stability of interconnected systems during periods of generation-load mismatch. (ITAE) is utilized as the objective function to be reduced in the process of tuning the gain parameters of the PID controller. The genetic algorithm thus proceeds as follows:
- Initiate a random population of chromosomes.
- Calculate the fitness function of every chromosome in the population.
- For the upcoming population, apply the following procedures: Selection: Based on the fitness function, defined as the process of choosing individuals from the current population to produce the new generation. Recombination: Crossover chromosomes and allows the exploration of new solution combinations by recombining genetic material from promising individuals. Mutation: The process of introducing random changes in individual solutions by mutating chromosomes. Acceptation: Refuse or accept a new candidate.
- Replace the old generation with a new generation.
- Test method criterion.
- Repeat Step 2 to step 5 till the stopping criterion is met.
Proposed PSO-Optimized Fuzzy PID Controller
The structure of the proposed hybrid PSO-Fuzzy PID technique is demonstrated in Fig. 9. As shown in this diagram, the system consists of a fuzzy controller connected in parallel with the conventional PID controller. The gains of PID are tuned by employing the PSO technique. fuzzy logic controller has two inputs: area control error (ACE) and variation in area control error ΔACE. AGC output is the frequency deviation caused by the load variation in the power grid.
Figs. 10 to 12 show the membership functions defined for the input variables: ACE and ΔACE, and the output variable Δf. In this paper, the Mamdani method of fuzzy inference mechanism and the centroid method of defuzzification approach are utilized. As shown in these figures, the input variables, ACE and ΔACE are represented by seven fuzzy linguistic variables: Largely Negative Value (LNV), Average Negative Value (ANV), Slightly Negative Value (SNV), Zero (Z), Slightly Positive Value (SPV), Average Positive Value (APV), and Largely Positive Value (LPV) respectively. The FLC output variable Δf is fuzzified into seven subsets as that of the input variables. The rule base developed for the fuzzy Controller is given in Table I. The range of variation of ACE, ΔACE and Δf are assumed to be in the range (−0.2 to +0.2).
LNV | ANV | SNV | Z | SPV | APV | LPV | |
---|---|---|---|---|---|---|---|
ACE | |||||||
LNV | LNV | LNV | LNV | LNV | ANV | SNV | Z |
ANV | LNV | LNV | LNV | ANV | SNV | Z | SPV |
SNV | LNV | LNV | ANV | SNV | Z | SPV | APV |
Z | LNV | ANV | SNV | Z | SPV | APV | LPV |
SPV | ANV | SNV | Z | SPV | APV | LPV | LPV |
APV | SNV | Z | SPV | APV | LPV | LPV | LPV |
LPV | Z | SPV | APV | LPV | LPV | LPV | LPV |
System Data and Simulation Findings
The efficacy of the proposed hybrid PSO-fuzzy PID method is analyzed on a two-area hybrid system discussed in Section 2, the data of which is given in the Appendix, by comparing its dynamic performance with those obtained using GA and PSO-optimized PID AGC. The GA and PSO parameters used for optimizing PID parameters of AGC are given in Tables II and III, respectively. The PSO method is utilized to improve the gain parameters of the fuzzy-PID controller of AGC. The data related to the genetic algorithm and the PSO techniques are shown in Tables II and III, respectively.
Population size | 60 |
---|---|
Maximum number of generations | 100 |
Elite count | 3 |
Mutation method | Adaptfeasible |
Crossover method | Arithmatic |
Crossover probability | 0.8 |
Creation method | Uniform |
Selection method | Tournament |
Imax | 50 |
---|---|
Number of particles | 15 |
c1 & c2 acceleration factors | 2 |
In both genetic and particle swarm optimization processes, the variation of Kp, Ki, Kd parameter values are assumed to be within the limits from −2 to 40 as it is observed to be in this range from the conventional simulation studies. Table IV shows the gain parameters of the proposed PSO-optimized fuzzy PID controller of the two area AGCs together with those corresponding to GA-PID and PSO-PID controllers. The Table also shows the final values of the respective fitness functions. These results correspond to a step load change of 0.1 per unit step load change in Area 1 at zero time instant. As can be seen from this Table, the proposed controller has a lower ITAE value than the other two controllers. Moreover, it can be noticed that the results of PSO and PSO-Fuzzy PID controller obtained parameters and ITAE value are near together when compared with GA which has slightly further results. The ITAE value obtained by GA is much higher than PSO and PSO-Fuzzy PID controller which means that the PSO and PSO-Fuzzy PID controller are much better than the GA. The variation of the fitness function of the proposed controller with the increasing number of iterations is shown in Fig. 13. As noticed from this figure, it converges within 50 iterations to the minimum ITAE value of 0.91672.
Algorithm | Area 1 | Area 2 | |||||
---|---|---|---|---|---|---|---|
Kp1 | Ki1 | Kd1 | Kp2 | Ki2 | Kd2 | ITAE | |
GA PID | 23.2193 | 2.9001 | 39.1807 | 7.9598 | 25.8566 | 22.0767 | 1.8510 |
PSO PID | 23.3879 | 0.5323 | 40 | 32.7343 | 8.4668 | 23.4933 | 1.1546 |
PSO-Fuzzy PID | 24.3840 | 0.6094 | 40 | 26.7018 | 5.6451 | 25.1473 | 0.91672 |
For a 0.1 per unit step load variation implemented in area 1 at the time instant, t = 0 second, the variation of frequency in both areas , as well as tie-line power exchange (∆Ptie) are demonstrated in Figs.14–16, respectively. These figures prove that the proposed PSO-Fuzzy PID method is more efficient in damping the oscillations compared to other controllers. From these figures and from Table V, it is obvious that the presented methodology is more efficient than others in handling dynamic issues related to settling time, peak overshoot and peak undershoot.
Controller | Settling time (S) | Overshoot | Undershoot | ||||||
---|---|---|---|---|---|---|---|---|---|
(Hz) | (Hz) | (pu) | (Hz) | (Hz) | (pu) | ||||
GA-PID | 13.3094 | 18.7857 | 19.0264 | 0.6386 | 0.3361 | 0.0077 | −0.8064 | −0.5398 | −0.0125 |
PSO-PID | 12.4063 | 15.9994 | 15.8336 | 0.2607 | 0.0601 | 0.0014 | −0.8062 | −0.5327 | −0.0126 |
Proposed PSO-Fuzzy-PID | 11.2823 | 13.8157 | 13.3891 | 0.1558 | 0.0194 | 0.0004 | −0.6941 | −0.4481 | −0.0106 |
To evaluate the system robustness, the sensitivity analysis is performed corresponding to ±50% variations from the nominal values in the following AGC system parameters:
- Area 2 governor time constant (Tg2) and Area 2 turbine time constant (TT2)
- Wind turbine time constants (TW2)
- Regulation parameter (R for all the power plants included in the model)
Table VI shows the performance of the PSO-Fuzzy PID AGC corresponding to these variations in terms of settling time, the maximum under and overshoots in , , and ∆Ptie, respectively. The comparison of the deviation of these variables from their standard values verifies the efficacy of the presented controller against system parameter deviations.
Parameter variation | Settling time | Overshoot | Undershoot | |||||||
---|---|---|---|---|---|---|---|---|---|---|
(Hz) | (Hz) | (pu) | (Hz) | (Hz) | (pu) | |||||
Nominal condition | 11.2823 | 13.8157 | 13.3891 | 0.1558 | 0.0194 | 0.0004 | −0.6941 | −0.4481 | −0.0106 | |
Tg2 & TT2 | −50% | 11.3261 | 14.5019 | 13.7198 | 0.1858 | 0.0259 | 0.0006 | −0.7220 | −0.4698 | −0.0111 |
+50% | 11.3357 | 14.9501 | 14.7373 | 0.2950 | 0.0683 | 0.0016 | −0.7781 | −0.5121 | −0.0121 | |
TW2 | −50% | 11.2072 | 13.5837 | 13.3975 | 0.1645 | 0.0201 | 0.0005 | −0.6923 | −0.4452 | −0.0105 |
+50% | 11.0313 | 12.8017 | 12.5398 | 0.1377 | 0.0128 | 0.0003 | −0.6779 | −0.4356 | −0.0103 | |
Ri | −50% | 11.2126 | 13.5012 | 13.2796 | 0.1441 | 0.0163 | 0.0004 | −0.6833 | −0.4381 | −0.0104 |
+50% | 11.1638 | 15.8841 | 12.8985 | 0.1450 | 0.0163 | 0.0003 | −0.6865 | −0.4428 | −0.0104 |
Conclusion
In this paper, a robust hybrid PSO-Fuzzy PID controller has been proposed for AGC of a two-area interconnected power system composed of thermal, hydro and diesel power plants together with the renewable energy resources: wind, solar PV energy conversion systems and in addition the electric vehicle loads. The proposed controller consists of the PSO-optimized PID controller in parallel with a fuzzy controller with ACE and changes in ACE as the inputs. The output is the area frequency deviations. The PSO optimization proceeds by minimizing the ITAE index value. Each of the input and output variables of the fuzzy controller are fuzzified into seven fuzzy subsets and the defuzzification is done by the centroid approach. A comparison of the dynamic performance of the proposed method for the two area AGC with those obtained using GA and PSO-optimized PID controllers indicates that the proposed method is significantly better than the other methods in damping the oscillations following the load disturbances. Further, the AGC controller remains practically robust in terms of the settling time, maximum and minimum overshoots of the frequency and the tie line power deviations of the interconnected power system irrespective of the variations in the system parameters.
References
-
Otchere IK, Kyeremeh KA, Frimpong EA. Adaptive PI-GA based technique for automatic generation control with renewable energy integration. 2020 IEEE PES/IAS Power Africa, Power Africa 2020, 2020. doi: 10.1109/PowerAfrica49420.2020.9219960.
DOI | Google Scholar
1
-
Gulzar MM, Iqbal M, Shahzad S, Muqeet HA, Shahzad M, Hussain MM. Load frequency control (LFC) strategies in renewable energy-based hybrid power systems: a review. Energies, 2022;15:1–23. doi: 10.3390/en15103488.
DOI | Google Scholar
2
-
Sharma Y, Saikia LC. Automatic generation control of a multiarea ST–thermal power system using grey wolf optimizer algorithm based classical controllers. Int J Electric Power Energy Syst. Dec. 2015;73:853–62. doi: 10.1016/J.IJEPES.2015.06.005.
DOI | Google Scholar
3
-
Bhaskar MK, Pal NS, Yadav VK. A comparative performance analysis of automatic generation control of multi-area power system using PID, fuzzy and ANFIS controllers. 2018 2nd IEEE International Conference on Power Electronics, Intelligent Control and Energy Systems, ICPEICES 2018, pp. 132–7, 2018. doi: 10.1109/ICPEICES.2018.8897477.
DOI | Google Scholar
4
-
Delassi A, Arif S, Mokrani L. Load frequency control problem in interconnected power systems using robust fractional PIλD controller. Ain Shams Engi J. 2018 Mar;9(1):77–88. doi: 10.1016/J.ASEJ.2015.10.004.
DOI | Google Scholar
5
-
Latif A, Hussain SMS, Das DC, Ustun TS. State-of-the-art of controllers and soft computing techniques for regulated load frequency management of single/multi-area traditional and renewable energy based power systems. Appl Energy. 2020;266(November 2019):114858. doi: 10.1016/j.apenergy.2020.114858.
DOI | Google Scholar
6
-
Sarkar MK, Dev A, Asthana P, Narzary D. Chattering free robust adaptive integral higher order sliding mode control for load frequency problems in multi-area power systems. IET Control Theory Appli. 2018;12:1216–27. doi: 10.1049/iet-cta.2017.0735.
DOI | Google Scholar
7
-
Prasad S, Purwar S, Kishor N. H-infinity based non-linear sliding mode controller for frequency regulation in interconnected power systems with constant and time-varying delays. IET Gener, Trans Distri. 2016;10:2771–84. doi: 10.1049/iet-gtd.2015.1475.
DOI | Google Scholar
8
-
Gulzar M, Rizvi S, Javed M, Sibtain D, ud Din RSalah. Mitigating the Load Frequency Fluctuations of Interconnected Power Systems Using Model Predictive Controller. Electronics (Basel). 2019 Feb;8(2):156. doi: 10.3390/electronics8020156.
DOI | Google Scholar
9
-
Khalid J, Ramli MAM, Khan MS, Hidayat T. Efficient load frequency control of renewable integrated power system: a twin delayed DDPG-based deep reinforcement learning approach. IEEE Access. 2022;10(April):51561–74. doi: 10.1109/ACCESS.2022.3174625.
DOI | Google Scholar
10
-
Golpîra H, Bevrani H, Golpîra H. Application of GA optimization for automatic generation control design in an interconnected power system. Energy Convers Manage. 2011;52(5):2247–55. doi: 10.1016/j.enconman.2011.01.010.
DOI | Google Scholar
11
-
Shayeghi H, Jalili A, Shayanfar HA. Multi-stage fuzzy load frequency control using PSO. Energy Convers Manage. 2008;49(10):2570–80. doi: 10.1016/j.enconman.2008.05.015.
DOI | Google Scholar
12
-
Guha PKRoy, Banerjee S. Application of backtracking search algorithm in load frequency control of multi-area interconnected power system. Ain Shams Engi J. 2018 Jun;9(2):257–76. doi: 10.1016/J.ASEJ.2016.01.004.
DOI | Google Scholar
13
-
Rajesh KS, Dash SS, Rajagopal R. Hybrid improved fireflypattern search optimized fuzzy aided PID controller for automatic generation control of power systems with multi-type generations. Swarm Evol Comput. 2019 Feb;44:200–11. doi: 10.1016/J.SWEVO.2018.03.005.
DOI | Google Scholar
14
-
Guha D, Roy PK, Banerjee S. Load frequency control of interconnected power system using grey wolf optimization. Swarm Evol Comput. 2016 Apr;27:97–115. doi: 10.1016/J.SWEVO.2015.10.004.
DOI | Google Scholar
15
-
Sriramula S, Reddy BR, Kalavathi MS. Fractional order ANN controller for lfc of evs integrated deregulated power system. IntJ Adv Res Engi Techno. 2020;11(10):13–27. doi: 10.34218/IJARET.11.10.2020.002.
Google Scholar
16
-
Debnath MK, Agrawal R, Tripathy SR, Choudhury S. Artificial neural network tuned PID controller for LFC investigation including distributed generation. Int J Numer Model: Electron Netw, Dev Fields. 2020;33(5):1–17. doi: 10.1002/jnm.2740.
DOI | Google Scholar
17
-
Priyadarshani S, Subhashini KR, Satapathy JK. Pathfinder algorithm optimized fractional order tilt-integral-derivative (FOTID) controller for automatic generation control of multisource power system. Microsyst Technol. 2021;27(1):23–35. doi: 10.1007/s00542-020-04897-4.
DOI | Google Scholar
18
-
Elmelegi A, Mohamed EA, Aly M, Ahmed EM, Mohamed AAA, Elbaksawi O. Optimized tilt fractional order cooperative controllers for preserving frequency stability in renewable energy-based power systems. IEEE Access. 2021;9:8261–77. doi: 10.1109/ACCESS.2021.3049782.
DOI | Google Scholar
19
-
Singh B, Adam Slowik SKB. Review on soft computing-based controllers for frequency regulation of diverse traditional, hybrid, and future power systems. 2023.
DOI | Google Scholar
20
-
Ismayil C, Sreerama Kumar R, Sindhu TK. Comparative analysis of genetic algorithm and fuzzy logic based automatic generation control of multi area power systems. Int Rev Model Simul. 2013;6(1):136–44.
Google Scholar
21
-
Prakash S, Sinha SK. ALFC of hybrid multi-generation power system using UC and TCPS by ANFIS control technique. Int J Elect. 2019;106(2):174–211. doi: 10.1080/00207217.2018.1519857.
DOI | Google Scholar
22
-
Sahu BK, Pati S, Mohanty PK, Panda S. Teaching-learning based optimization algorithm based fuzzy-PID controller for automatic generation control of multi-area power system. Appl Soft Comput J. 2015 Aug;27:240–9. doi: 10.1016/j.asoc.2014.11.027.
DOI | Google Scholar
23
-
Prakash S, Sinha SK. Load frequency control of three area interconnected hydro-thermal reheat power system using artificial intelligence and PI controllers. Int J Eng, Sci Technol. 2018 Mar;4(1):23–37. doi: 10.4314/ijest.v4i1.4s.
DOI | Google Scholar
24
-
Sai Kalyan CN, Goud BS, Reddy CR, Kumar MK, Bajaj M, El-Naggar MF, et al. Performance assessment of open-loop and closed-loop generation rate constraint models for optimal LFC of the three-area reheat thermal system. Front Energy Res. 2022 Jun;10. doi: 10.3389/fenrg.2022.920651.
DOI | Google Scholar
25
-
Arya Y, Kumar N, Dahiya P, Sharma G, Çelik E, Dhundhara S, et al. Cascade-IλDμN controller design for AGC of thermal and hydro-thermal power systems integrated with renewable energy sources. IET Renew Power Gener. 2021;15(3):504–20. doi: 10.1049/rpg2.12061.
DOI | Google Scholar
26
-
Yang J, Zeng Z, Tang Y, Yan J, He H, Wu Y. Load frequency control in isolated micro-grids with electrical vehicles based on multivariable generalized predictive theory. Energies (Basel). 2015;8(3):2145–64. doi: 10.3390/en8032145.
DOI | Google Scholar
27
-
Das DC, Roy AK, Sinha N. GA based frequency controller for solar thermal-diesel-wind hybrid energy generation/energy storage system. Int J Electr Power Energy Syst. 2012;43(1):262–79. doi: 10.1016/j.ijepes.2012.05.025.
DOI | Google Scholar
28
-
Dey PP, Das DC, Latif A, Hussain SMS, Ustun TS. Active Power Management of Virtual Power Plant under Penetration of Central Receiver Solar Thermal-Wind Using Butterfly Optimization Technique. Sustainability. 2020 Aug;12(17):6979. doi: 10.3390/su12176979.
DOI | Google Scholar
29
-
Latif A, Das DC, Ranjan S, Barik AK. Comparative performance evaluation of WCA-optimised non-integer controller employed with WPG-DSPG–PHEV based isolated two-area interconnected microgrid system. IET Renew Power Gener. 2019;13(5):725–36. doi: 10.1049/iet-rpg.2018.5419.
DOI | Google Scholar
30
-
Kumar A, Shankar G. Quasi-oppositional harmony search algorithm based optimal dynamic load frequency control of a hybrid tidal-diesel power generation system. IET Gener, Transm Dis. 2018;12(5):1099–108. doi: 10.1049/iet-gtd.2017.1115.
DOI | Google Scholar
31
-
Sahin E. Design of an Optimized Fractional High Order Differential Feedback Controller for Load Frequency Control of a Multi-Area Multi-Source Power System with Nonlinearity. IEEE Access. 2020;8:12327–42. doi: 10.1109/ACCESS.2020.2966261.
DOI | Google Scholar
32
-
Rul N, Abdullah H, Song HM. Optimal load frequency control in single area power system using pid controller based on bacterial foraging & particle swarm optimization. ARPN J Engi Appli Sci. 2015;10(22). [online]. Available: www.arpnjournals.com.
Google Scholar
33